Description
- 10/100 BaseT Connection
Connect the device to a network using a 10 or 100 BaseT connection
- Battery failure notification
Provides early-warning fault analysis on batteries enabling timely preventive maintenance
- Green mode
Patent-pending operating mode that bypasses unused electrical components in good power conditions to achieve very high operating efficiency without sacrificing any protection.
- LCD graphics display
Text and mimic diagrams that display modes of operation, system parameters and alarms.
- Avoids costly power problems by keeping your IT equipment and data protected and available.
Network grade power conditioning protects from damaging surges and disruptive noise. The double conversion architecture provides tight voltage regulation, frequency regulation ,and zero transfer time to battery during power events.
- Save time with easy and convenient remote/network accessibility.
Network manageable via serial, USB or Ethernet. Includes Powerchute® Software for convenient monitoring and control, safe operating system shutdown, and innovative energy management capabilities.
- Low operating and maintenance costs with proven reliability and intelligent battery management.
Intelligent battery management, pioneered by APC, maximizes battery performance and life through intelligent, precision temperature compensated charging. Automatic self tests insure battery reliability and warn customers in advance of battery replacement. Convenient, easy to connect, hot-swappable battery modules provide battery replacement without powering down.
- Peace of mind that comes with full equipment compatibility and reliability of a leader
Provides pure sine wave output which is recommended by server manufacturers using active power factor corrected (PFC) power supplies. Safety agency tested and approved means that you can deploy Smart-UPS with confidence that they meet or exceed the industry’s most rigorous standards.
- Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
- Scalable runtime
Allows additional run time to be quickly added as needed.
- Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
- Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
- Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
- Automatic restart of loads after UPS shutdown
- LED status indicators
Quickly understand unit and power status with visual indicators.
- Serial connectivity
Provides management of the UPS via a serial port.
- InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
- SmartSlot
Customize UPS capabilities with management cards.
- Network manageable
Provides remote power management of the UPS over the network
Output power capacity
10.0kWatts / 10.0kVAMax Configurable Power (Watts)
10.0kWatts / 10.0kVANominal Output Voltage
230VOutput Voltage Distortion
Less than 2%Output Frequency (sync to mains)
50/60Hz +/- 3 HzOther Output Voltages
220, 240Load Crest Factor
3 : 1Topology
Double Conversion OnlineWaveform type
Sine waveOutput Connections
(6) IEC 320 C13 (Battery Backup)(4) IEC 320 C19 (Battery Backup)(1) Hard Wire 3-wire (H N + G) (Battery Backup)(3) IEC Jumpers (Battery Backup)Bypass
Internal Bypass (Automatic and Manual)Input
Nominal Input Voltage
230V, 400V 3PHInput frequency
40 – 70 Hz (auto sensing)Input Connections
Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)Input voltage range for main operations
160 – 275VInput voltage adjustable range for mains operation
100 – 275 (half load), 173 – 476 (half load)VOther Input Voltages
220, 240, 380, 415Batteries & Runtime
Battery type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproofTypical recharge time
1.5hour(s)Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)Replacement Battery
Expected Battery Life (years)
3 – 5RBC Quantity
2Extendable Run Time
1Battery Volt-Amp-Hour Capacity
1805Extended Run Options
Communications & Management
Interface Port(s)
RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USBControl panel
Multi-function LCD status and control consoleAudible Alarm
Audible and visible alarms prioritized by severityEmergency Power Off (EPO)
YesAvailable SmartSlot™ Interface Quantity
1Surge Protection and Filtering
Surge energy rating
480JoulesPhysical
Maximum Height
43.2CMMaximum Width
26.3CMMaximum Depth
71.5CMNet Weight
111.82KGOperating Temperature
0 – 40 °COperating Relative Humidity
0 – 95 %Operating Elevation
0-3000metersStorage Temperature
-15 – 45 °CStorage Relative Humidity
0 – 95% non-condensing %Storage Elevation
0-15000metersAudible noise at 1 meter from surface of unit
55.0dBAOnline thermal dissipation
1947.0BTU/hrProtection Class
IP 20Standard warranty
3 years repair or replace (excluding battery) and 2 years for battery
Reviews